SET-Eco 1A have Mini size AC Drive to save the installation space, this series inverter uses a simplified vector control technology to achieve extensive application of functional blocks.It meets the requirements for high torque and improves the dynamic response and motor control features by using automatic fully frequency band and output torque compensation.
Item | Specifications | |
Input | Rated voltage; Frequency |
SET-Eco 1A G3: 380V ~ 440V; 50Hz/60Hz SET-Eco 1A G1: 200V ~ 240V; 50Hz/60Hz |
Permissible fluctuation range | Voltage contant fluctuate ≤±10%, Transient fluctuate:-15% ~+10%, out of balance voltage rate:≤3%, frequency fluctuation:≤5% | |
Output | Rated voltage | SET-Eco 1A G1: 0~200V/240V SET 1A G3: 0~380V/440V |
Rated power | SET-Eco 1A G1: 0.40~2.2KW SET-Eco 1A G3:0.75~2.2KW |
|
Frequency | 0Hz~650Hz | |
Control functions | Modulation mode | Flux vector PWM modulation |
Speed range | 1:100 | |
Starting torque | 180% rated torque at 0.5HZ | |
Accuracy of speed at steady state | ≤±0.5% rated synchronous speed | |
Torque boost | Auto torque boost, Manual toque boost | |
Acc/Dec curve | Linear | |
Jog | Jog frequency, Acc/Dec time, Jog interval are adjustable |
|
Multi-speed operation | 15 sections of frequency. Able to achieve through the built-in PLC or terminals. | |
Closed-loop control | Analog closed-loop | |
Auto voltage regulation | Constant output voltage even if electric network voltage fluctuates | |
Auto current limiting | Operating current is limited automatically to avoid frequent tripping of the inverter | |
Auto carrier-wave regulation | Adjust the carrier frequency automatically according to the load characteristic; | |
Special function | Internal counter | Counting the external pulse signal through X terminals |
Methods of inputting commands | keypad panel, terminals and serial port | |
Methods of setting up frequency | Digital setting, AIand communication | |
Auxiliary frequency | Flexible auxiliary frequency selectable | |
Analog output terminals | 0/4~20mA and 0/2~10V(selectable) | |
Protection function | Phase loss failure, Over/Under current, Over/Under voltage protection, Overheat and overload protection | |
Environment | Operating environment | In-door, not subject to direct sunlight, no dust, corrosive, flammable gas, oil mist, steam, water, or salt, etc |
Altitude | Less than 1000m, derating is required more than 1000m | |
Ambient temperature | -10°C~+40°C, derating is required from 40~50°C; Increase every 1 above 40°C, derating 2%, highest temperature allowed: 50°C |
|
Humidity | Less than 95% RHno condensing | |
Vibration | Less than5.9m/s2(0.6g) | |
Storage temperature | -40 ~+70 | |
Enclosure | Protection level | IP20 |
Cooling | Fan cooling, natural cooling | |
Mounting mode | Mounted in a cabinet |
Mark | Function&Setting | Default |
CN8- CN10 | Analog I/O, digital I/O, relay outputs | |
CN4 | CCI current/voltage input selection I:0~20mA current signal V:0~10V voltage signal |
0~+10V |
CN5 | 485 terminal resistor selection: ON: 120Ω terminal resistor OFF: No terminal resistor. |
No terminal resistor |
CN6 | AO current/voltage input selection 0/4~20mA: AO current signal 0/2~10V: AO voltage signal |
0~+10V |
Category | Terminals | Name | Function | Specification |
Communication | 485+ | RS485co mmunication port | RS485+ (differential signal) | Standard RS-485 communication port, Please use twisted-pair cable or shielded cable |
485- | RS485-(differential sig nal) | |||
Analoginput | AI | Analog input | Accepting analog voltage/current input.CN4 can select voltage or current input mode,Voltage input mode is the default (Reference ground: GND) | Input voltage range:0~10V (input resistance:100kΩ) Input current range:0~20mA (input resistance:500Ω) resolution:1/2000 |
Analog output | AO | Analog output | Be able to output analog voltage/current, Jumper CN6 can select voltage or current input mode. Voltage input mode is the default mode. Refer to F6.04 for details (reference ground: GND) | Output current range: M 0/4~20mA Output voltage range: 0/2~10V |
Digital input | X1~X5 | Multi-func tional digital inputs 1~ 5 | Can be defined as multi-functional digital inputs, see Section 7.6 Reference ground: COM |
Optical-isolator 2-way input input resistance: 2kΩ maximum input frequency: 200Hz Input voltage range: 9~30V |
PLC | Common terminal | Common terminal for multi-functional inputs | ||
P24 | +24V supply | Providing +24V power supply | Output:+24V,set point accuracy:±10% Max output current:200mA |
|
COM | +24V common terminal | Isolated internally with GND | Isolated internally with GND | |
Digital input | Y1 | Open collector output 1 | Programmable terminals, defined as multi-function digital outputs, see Section 7.7. | Optical-isolator output: 24VDC/50mA |
Power supply | +10V | +10V power supply | Provide +10V power supply | Output: +10V, Setpoint accuracy: ±10% Max. output current: 100mA |
GND | GND of +10V power supply | reference ground of analog signal and 10V power supply | Isolated internally with COM | |
Others | TA/TB/T C | Relay output | TA, TB and TC can be defined as multi-functional digital output signals. | TA-TB:normally closed; TA-TC:normally open Contact capacity:250Vac/2A (COSφ=1),250Vac/1A (COSφ=0.4),30 Vdc /1A |